Answering now · 24 hours, 7 days

Smell gas? Leave the house, then call 911 or your gas utility.

(864) 415-7482
Gas Guys Plumbing & Heating

Water heaters

Gas Line Sizing for a Tankless Water Heater

A gas tankless water heater can fire at close to five times what the tank it replaces did. The pipe that fed the tank was almost never sized for that. Here is how to tell whether your gas supply can keep up, what happens when it cannot, and the ways to fix it.

The short answer

  • A gas tank heater burns about 40,000 BTU an hour. Whole-house tankless units commonly run from about 150,000 to 199,000.
  • The pipe has to carry the tankless unit plus every other gas appliance that could run at the same time, over the full length of the run.
  • The meter has a capacity too. A tankless unit can push a house past it, and only the utility can change the meter.
  • An undersized supply shows up as error codes, temperature swings and lukewarm water when two fixtures run.

Why tankless needs so much gas

A tank heater stores hot water and reheats it slowly with a small burner. A tankless heater stores nothing, so it has to heat water from tap temperature to shower temperature in the few seconds it takes to pass through the heat exchanger. That takes a very large burner, and the burner only fires at full input when the demand is high.

Natural gas carries roughly 1,000 BTU per cubic foot, so a 199,000 BTU unit at full fire needs close to 200 cubic feet of gas an hour. The tank it replaced needed about 40. The number to size from is the maximum input on the unit's rating plate, not the average.

Add up the whole house

Gas lines are sized for everything that can run at once. Make a list from the labels:

  • The tankless unit, at its maximum input
  • The furnace, often somewhere in the range of 40,000 to 100,000 BTU
  • A range and oven
  • A dryer
  • Gas logs, a grill, a pool heater or a generator, if you have them

Pipe size and length

The fuel gas code sizing tables give the gas a pipe can carry by its size, its material and the length of the run, with a small allowed pressure drop. The longer the run, the less a given pipe carries. A half-inch line that fed a 40,000 BTU tank across a basement is nowhere near big enough for a tankless unit at the same spot, and the trunk line it tees into may be undersized for the new total as well.

The manufacturer adds a requirement of its own: a minimum gas inlet pressure, in inches of water column, measured at the heater while it runs at full fire alongside the other appliances. A line can pass a static pressure check with everything off and still fall short once the burner opens up. A proper install measures it under load.

CSST and black iron have different sizing tables, and CSST in particular is sized by its own maker's charts. Mixing them on one system is common and fine, as long as each piece is sized for what it carries.

Meter capacity

Your meter and service line have a rated capacity, and many homes have a residential meter rated around 250 cubic feet an hour. A furnace, a range, a dryer and a 199,000 BTU tankless heater can add up past that. When the total is over the meter, it is the utility's call, whether that is Piedmont Natural Gas or Greer CPW. They may set a larger meter or change how gas is delivered to the house.

Utility work runs on the utility's schedule, so the load question should be settled before the unit is bought and the old tank is pulled.

What an undersized line does

A tankless heater that cannot get enough gas tells you in a few ways:

  • Ignition or flame-failure error codes, especially when the furnace is running
  • Water that goes hot, then lukewarm, then hot again during a shower
  • Plenty of hot water at one tap, but not at two at once
  • Furnace or range flames that shrink or flutter when the tankless fires
  • A unit that runs fine in summer and falls short on cold January mornings, when it needs every BTU

The fixes

The usual answer is a new, properly sized line from the meter, or from a point near the meter where the pipe is big enough, to the heater. On some houses the trunk line toward the meter is upsized so the whole system can carry the new total. Where the meter is the limit, the utility handles the meter. In some cases, a lower-input unit sized for how many showers you actually run at once is the better fit.

Whatever the fix, it is new gas piping, so it is permitted, pressure-tested and inspected, and the heater's inlet pressure is checked at full fire before the job is done.

When to call a pro

Call before you buy a tankless water heater, so the whole-house gas load, the pipe and the meter can be checked against the unit you want. Call too if a tankless unit you already have throws error codes or swings in temperature when other gas appliances run.

Call (864) 415-7482, 24/7

Questions

More questions

Still not sure? Call (864) 415-7482. A person answers 24/7. Or browse every common question.

Does a tankless water heater need a bigger gas line?

Usually. Most whole-house units draw several times what a tank does, and the half-inch line that fed the tank is rarely enough on its own. The line is sized for the unit plus every other gas appliance, over the length of the run.

Can I keep my half-inch gas line for a tankless heater?

Rarely, and only if the run is very short and the rest of the system has capacity to spare. It has to be checked against the code sizing tables and confirmed by measuring inlet pressure while the heater runs at full fire.

Will I need a bigger gas meter for a tankless water heater?

Sometimes. If the total of all your gas appliances is more than the meter is rated for, the utility decides whether to upgrade it. That should be checked before the unit is bought.

Why does my tankless heater give error codes when the furnace is on?

That pattern points to a gas supply that cannot carry both at once. The pipe, the meter or both may be undersized for the combined load. It needs a pressure check under load to confirm.

24/7 · Spartanburg County & western NC

Need a plumber or a gas line looked at?

Call any hour and a person answers. Or send the details and a photo and we will call you back.

(864) 415-7482
  • Real people answering 24/7
  • Transparent, up-front pricing
  • Fully licensed & insured in SC & NC
  • Locally owned & operated
  • Financing available

Request service

Urgent? Call (864) 415-7482 instead.